Introduction to Schneider RE48ATM12MW On-delay Timing Relay
On-delay timing relays, also known as delay-on energize relays, are fundamental components in control circuits. They introduce a delay between the application of input power and the activation of output contacts, facilitating intricate timing operations.
Features of Schneider RE48ATM12MW
This relay boasts a wide timing range from 0.02 seconds to 300 hours, making it versatile for diverse time-dependent applications. It operates within a voltage range of 24 to 240 volts AC, ensuring compatibility with common power systems. With 2 output contacts (2 OC), it offers flexibility in connecting to external devices.
Applications of On-delay Timing Relays
The Schneider RE48ATM12MW finds applications across industrial automation sectors, where precise timing is critical for coordinated operations. It is extensively used in control systems, motor control panels, and timing sequences requiring delayed activation.
How Schneider RE48ATM12MW Works
Upon receiving input power, this relay initiates a time delay before engaging its output contacts. This delay mechanism is crucial for synchronizing processes or preventing simultaneous activations, contributing to operational efficiency and safety.
Benefits of Using Schneider RE48ATM12MW
- Precision Timing: Ensures accurate time delays for optimal system performance.
- Enhanced Control: Facilitates sequential operations, reducing manual intervention and errors.
Comparison with Other Timing Relays
Compared to conventional timing relays, the Schneider RE48ATM12MW stands out with its extended timing range, robust design, and reliable performance. Its dual output contacts provide redundancy and versatility in control applications.
Installation and Maintenance Tips
Proper installation of the Schneider RE48ATM12MW involves following manufacturer guidelines for wiring and parameter settings. Routine maintenance includes periodic checks for functionality, ensuring consistent and reliable operation over time.
Conclusion
In conclusion, the Schneider RE48ATM12MW on-delay timing relay represents a sophisticated solution for time-sensitive applications in electrical engineering and automation. Its advanced features, precise timing capabilities, and compatibility make it a preferred choice for control systems across various industries.
Unique FAQs
- Q: Can the timing range of the Schneider RE48ATM12MW be adjusted?
- A: Yes, the timing range can be adjusted based on specific application requirements.
- Q: Is the installation of this timing relay complex?
- A: Installation is straightforward, but it’s recommended to follow the provided guidelines for accurate setup.
- Q: What are the typical voltage ratings for this relay?
- A: The Schneider RE48ATM12MW operates within a voltage range of 24 to 240 volts AC.
- Q: How does the delay mechanism work in this timing relay?
- A: The relay introduces a delay between input power application and output contact activation, ensuring controlled timing sequences.
- Q: Can this relay be used in conjunction with other control devices?
- A: Yes, it can be integrated into complex control systems alongside other devices for comprehensive automation solutions.
Additional information
brands | Schneider Electric |
---|---|
Range of product | Harmony Timer Relays |
Product or component type | Single function relay |
Electrical connection | Plug-in sub-base 8 pin(s) |
Component name | RE48 |
Time delay range | 5…300 h 2…120 min 0.5…30 h 0.2…12 h 0.2…12 min 0.2…12 s 0.5…30 min 2…120 h 2…120 s 0.02…1.2 s 0.5…30 s 5…300 s 0.05…3 s 5…300 min |
Control type | Selector switch front panel |
Housing material | Self-extinguishing |
Mechanical durability | 30000000 cycles |
Net weight | 0.14 kg |
Product front plate size | 48 x 48 mm |
Temperature drift | +/- 0.02 %/°C of the maximum setting value conforming to IEC 61812-1 |
Voltage drift | +/- 0.2 %/V of the maximum setting value at 48…240 V +/- 1 %/V of the maximum setting value at 24…48 V |
Minimum pulse duration | 20 ms |
Pick up duration | 55 ms |
On-load factor | 100% |
Power consumption in W | 0.5 W at 24 V 1.7 W at 240 V |
Output voltage | 240 V at 5 A AC-12 30 V at 2 A DC-13 240 V at 1.5 A AC-15 |
Marking | CE |
Mounting support | Panel mounted: system supplied with the product Base mounted: socket |
discrete output type | Relay |
Standards | 73/23/EEC 93/68/EEC EN 50082-1/2 89/336/EEC EN 50081-1/2 IEC 61812-1 IEC 60669-2-3 |
Product certifications | UL cULus C-Tick CSA |
Humidity drift | +/- 0.05 %/%RH of the maximum setting value conforming to IEC 61812-1 |
Immunity to voltage dips | 30 % / 10 ms conforming to IEC 61000-4-11 60 % / 100 ms conforming to IEC 61000-4-11 95 % / 5 s conforming to IEC 61000-4-11 |
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 5.7 cm |
Package 1 Width | 10.5 cm |
Package 1 Length | 6.2 cm |
Package 1 Weight | 126 g |
Unit Type of Package 2 | S02 |
Number of Units in Package 2 | 30 |
Package 2 Height | 15 cm |
Package 2 Width | 30 cm |
Package 2 Length | 40 cm |
Package 2 Weight | 4.252 kg |
Sustainable offer status | Green Premium product |
REACh Regulation | REACh Declaration |
EU RoHS Directive | Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS Declaration |
Mercury free | Yes |
China RoHS Regulation | China RoHS declaration |
China RoHS declaration | Yes |
Environmental Disclosure | Product Environmental Profile |
Circularity Profile | End of Life Information |
Warranty | 18 months |
Reviews
There are no reviews yet.